CCW340 technical data for cold water coil – accessories
Technical Data
Test pressure 3000 kPa
Max. operating pressure 1600 kPa
Number of rows of pipes 4
Number of circuits 8
Face area (HxW) 500 x 610 mm
Pipe connection DN25 (1’’)
Fin spacing 2.8 mm
Weight, non-insulated (without uid) 39 kg
Weight, insulated model (without uid) 72 kg
Water content 3.5 l
Capacity diagrams for cold water coil
Conditions
Supply water temperature 6 °C
Return water temperature 12 °C
Tolerance of calculated results ± 10 %
Volume ow ratio 1.0
Cooling recovery 100 %
NB:
The output values in the table below are for a
glycol content of 25 %.
VEX340 (2000 m
3
/h) / CCW340 cold water coil (100 % cooling recovery)
Outdoor
air temp./
humidity
Room temp./
humidity
Temp. and
humidity
after exchanger
CCW
output
Supply air
temp./humidity
Water
ow
p CCW
K
vs
p K
vs
p
air side
[°C / %] [°C / %] [°C / %] [kW] [°C / %] [l/h] [kPa] [kPa] [Pa]
28 / 50 24 / 50 24.7 / 61 9 16.8 / 84 1399 13.5 2.5 31 40
32 / 40 26 / 50 27.1 / 53 10.6 17.2 / 81 1668 18 2.5 44 40
We recommend the cold water coil requirements are precisely calculated using the EXselect product
selection software tool on our website, which also includes more comprehensive calculation data.
Example of calculated values for the cold water coil