CDA CST Instalační manuál

Procházejte online nebo si stáhněte Instalační manuál pro Pračka CDA CST. CDA CST Installation manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - LARGE DEHUMIDIFYING DRYERS

OPERATION AND INSTALLATION MANUAL WD/SDA/CDA SERIES 350 - 2100 CFM LARGE DEHUMIDIFYING DRYERS IMPORTANT: PLEASE READ CAREFULLY BEFORE ATTEMPTING TO

Strany 2

350-2100 cfm Dryers Chapter 1: Safety 9 of 58 1-4 Responsibility These machines are constructed for maximum operator safety when used under standa

Strany 3

350-2100 cfm Dryers Chapter 1: Safety 10 of 58 Learn and always use safe operation. Cooperate with co-workers to promote safe practices. Immediatel

Strany 4 - Shipping Info

350-2100 cfm Dryers Chapter 1: Safety 11 of 58 Before removing, adjusting, or replacing parts on a machine, remember to turn off all electric suppl

Strany 5 - Table of Contents

350-2100 cfm Dryers Chapter 2: Functional Description 12 of 58 Chapter 2: Functional Description 2-1 Models Covered in This Manual This manual pr

Strany 6

350-2100 cfm Dryers Chapter 2: Functional Description 13 of 58 2-5 The Closed Loop Drying System ACS dryers force hot, dry air through the resin i

Strany 7 - Chapter 1: Safety

350-2100 cfm Dryers Chapter 2: Functional Description 14 of 58 When a desiccant bed is on-line, it absorbs moisture from the process air. In time,

Strany 8 - PE Protected Earth

350-2100 cfm Dryers Chapter 2: Functional Description 15 of 58 Figure 3: ???????? ?EABCREAR VIEWTOP VIEWD34" RADIUSDESICCANT TOWER(LEFT SIDE)

Strany 9

350-2100 cfm Dryers Chapter 2: Functional Description 16 of 58 GF IHLEFT18"MINIMUMMAINTENANCECLEARANCE24"SUGGESTEDMINIMUMVERTICALCLEARAN

Strany 10 - 1-4 Responsibility

350-2100 cfm Dryers Chapter 3: Installation 17 of 58 Chapter 3: Installation 3-1 Work Rules The installation, operation, and maintenance of this e

Strany 11

350-2100 cfm Dryers Chapter 3: Installation 18 of 58 ; Keep the delivery (to the drying hopper) hose as short as possible to minimize heat loss. I

Strany 12 - 1-5 Responsibility

Please note that our address and phone information has changed. Please reference this page for updated contact information. These manuals are obsolet

Strany 13 - 2-4 Optional Features

350-2100 cfm Dryers Chapter 3: Installation 19 of 58 Figure 5: Typical Control Panel Process Heater AmpsRegen Heater AmpsRedundant High Temp Safet

Strany 14 - 2-6 What is Desiccant?

350-2100 cfm Dryers Chapter 4: Control Panel 20 of 58 Chapter 4: Control Panel 4-1 Control Panel Indicator Lights PROCESS BLOWER ON This indic

Strany 15 - Figure Two:

350-2100 cfm Dryers Chapter 4: Control Panel 21 of 58 ; The alarm mode and value are factory-set to track 25°F below the process setpoint. The ala

Strany 16 - TOP VIEW

350-2100 cfm Dryers Chapter 4: Control Panel 22 of 58 VALVE POSITION ERROR A pair of position switches confirm proper shifting of the valves. If

Strany 17 - WD Dryer Dimensions

350-2100 cfm Dryers Chapter 4: Control Panel 23 of 58 ; If one or two of a heater's three meters indicates a low reading, a burned-out heater

Strany 18 - Chapter 3: Installation

350-2100 cfm Dryers Chapter 4: Control Panel 24 of 58 Figure 6: Process Air Temperature Controller

Strany 19 - 3-6 Drying Hopper Air Trap

350-2100 cfm Dryers Chapter 4: Control Panel 25 of 58 4-5 Temperature Controller LED Indicators Process Value Numeric LED During normal operatio

Strany 20 - SeriesWD

350-2100 cfm Dryers Chapter 4: Control Panel 26 of 58 4-6 Temperature Controller Keys – (See Figure 5 in Section 3-6) LEVEL KEY When pre

Strany 21 - Chapter 4: Control Panel

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 27 of 58 Chapter 5: Startup, Shutdown & Operation 5-1 Pre-Startup Checks ;

Strany 22

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 28 of 58 6. If the dryer has an aftercooler, make sure there is proper flow of co

Strany 23 - 4-2 Switches and Meters

Bulletin Number ii Write Down Your Serial Numbers Here For Future Reference: _________________________ _______________

Strany 24 - 4-3 PLC Control

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 29 of 58 The low temperature alarm value is a deviation of the process air tempera

Strany 25

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 30 of 58 5-9 Changing the Display from Fahrenheit to Centigrade To change the dis

Strany 26

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 31 of 58 5-11 Regeneration Monitoring System Signal Processor Dryer models 350 t

Strany 27

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 32 of 58 • Press again to move one digit to the right. Then press to display t

Strany 28 - 5-2 Startup

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 33 of 58 Setting the Current Day of the Week, Hour and Minute: 1. Apply main pow

Strany 29 - 5-3 Shutdown

350-2100 cfm Dryers Chapter 5: Startup, Shutdown & Operation 34 of 58 7. Press once. The hour and minute display returns to zeroes and the hou

Strany 30

350-2100 cfm Dryers Chapter 6: Maintenance 35 of 58 Chapter 6: Maintenance 6-1 Servicing the Process Air Filters (Models 350-700) WARNING: Oper

Strany 31

350-2100 cfm Dryers Chapter 6: Maintenance 36 of 58 to remove all dirt and suds (less than 40 psi, no nozzle). If the clean or downstream side of t

Strany 32

350-2100 cfm Dryers Chapter 6: Maintenance 37 of 58 service. Satisfactory filtration should be obtained through the second or third washing , howev

Strany 33

350-2100 cfm Dryers Chapter 6: Maintenance 38 of 58 9. Remove the restriction from the filter element and re-install the clean filter. The alarm l

Strany 34

Bulletin Number iii Shipping Info Unpacking and Inspection You should inspect your dryer for possible shipping damage. Thoroughly check the equipm

Strany 35

350-2100 cfm Dryers Chapter 6: Maintenance 39 of 58 • Noticeable amounts of desiccant in the beds is a medium-brown color, or darker. If any of t

Strany 36 - Chapter 6: Maintenance

350-2100 cfm Dryers Chapter 6: Maintenance 40 of 58 Figure 6: Desiccant Amounts Required Dryer Desiccant Required per Tower Model Large Bead Sm

Strany 37

350-2100 cfm Dryers Chapter 6: Maintenance 41 of 58 6-10 Regeneration Heater Replacement Procedure Dryer models 350 through 2100 Dryers have four

Strany 38 - WARNING:

350-2100 cfm Dryers Chapter 6: Maintenance 42 of 58 6-11 Restoring a Temperature Controller to the Factory Setup If the control's pre-set pa

Strany 39

350-2100 cfm Dryers Chapter 6: Maintenance 43 of 58 Display Characters Sensor Type Switch Position Temp Range °C °F Thermocouple Type R 0

Strany 40

350-2100 cfm Dryers Chapter 6: Maintenance 44 of 58 11. Slide the control chassis back into the control housing. The remaining parameters are se

Strany 41

350-2100 cfm Dryers Chapter 6: Maintenance 45 of 58 Figure 7: Factory Pre-Set Control Parameters Parameter Setting Levels Parameter Description

Strany 42

350-2100 cfm Dryers Chapter 6: Maintenance 46 of 58 Figure 8: Process Temperature Control Error Messages Message Cause Control Output Alarm

Strany 43 - Protect (SW101)

350-2100 cfm Dryers Chapter 6: Maintenance 47 of 58 Figure 9: Regeneration Monitor Signal Processor Error Messages Item Condition Error Outpu

Strany 44

350-2100 cfm Dryers Chapter 6: Maintenance 48 of 58 6-12 Regeneration Monitor Advanced Programming The regeneration monitor has three menu levels,

Strany 45

Bulletin Number iv Table of Contents CHAPTER 1: SAFETY... 6 1-1 How to Use This Man

Strany 46 - Parameter

350-2100 cfm Dryers Chapter 6: Maintenance 49 of 58 LEVEL 1 In this level, the four setpoints can be changed, plus Hysteresis, Input Shift and Sec

Strany 47

350-2100 cfm Dryers Chapter 6: Maintenance 50 of 58 Press after appears on the LED display. Use and to set the value. Then press to save th

Strany 48

350-2100 cfm Dryers Chapter 6: Maintenance 51 of 58 LEVEL 2 In this level, parameters such as the type of temperature sensor connected to the rege

Strany 49 - Level 0 Level 1

350-2100 cfm Dryers Chapter 7: Troubleshooting 52 of 58 Chapter 7: Troubleshooting PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION Little or no air c

Strany 50 - Security Protection

350-2100 cfm Dryers Chapter 7: Troubleshooting 53 of 58 PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION Loss or reduction of process air temperature.

Strany 51

350-2100 cfm Dryers Chapter 7: Troubleshooting 54 of 58 PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION Material in drying hopper cakes, or meltdown

Strany 52 - Display Refresh Cycle

350-2100 cfm Dryers Chapter 8: Appendix 55 of 58 Chapter 8: Appendix 8-1 Customer Satisfaction Warranty Program The terms and conditions of the wa

Strany 53 - Chapter 7: Troubleshooting

350-2100 cfm Dryers Chapter 8: Appendix 56 of 58 -Notes-

Strany 54

350-2100 cfm Dryers Chapter 8: Appendix 57 of 58 Preventive Maintenance Checklist Dehumidifying Dryers Dryer Model # Serial # EVERY WEEK Date/ B

Strany 55

350-2100 cfm Dryers Chapter 8: Appendix 58 of 58 8-2 Technical Assistance Parts Department Call toll-free 7am–5pm CST [800] 423-3183 or call [630]

Strany 56 - Chapter 8: Appendix

Bulletin Number v 5-5 Setting the High and Low Temperature Alarms ... 28 5-6 Temperature Co

Strany 57 - -Notes

350-2100 cfm Dryers Chapter 1: Safety 6 of 58 Chapter 1: Safety 1-1 How to Use This Manual Use this manual as a guide and reference for installin

Strany 58 - Dehumidifying Dryers

350-2100 cfm Dryers Chapter 1: Safety 7 of 58 1-2 Safety Tag Information Dryer Safety Tags Hot! Read Operation and Installation

Strany 59 - 8-2 Technical Assistance

350-2100 cfm Dryers Chapter 1: Safety 8 of 58 1-3 Warnings and Precautions Our equipment is designed to provide safe and reliable operation when

Komentáře k této Příručce

Žádné komentáře